• 8-36VDC supply
• 2-4 Amp output rating
• LED diagnostics
• 3NO + 1NC output contacts
• Automatic/manual-monitored reset
The SRL-3 Safety relay has a 3 channel, low voltage inputs, three normally open control contact outputs and one normally closed indication contact.
With LED indication to speed up fault finding and a slim 22.5mm DIN rail mounting enclosure the SRL-3 takes up minimum control panel space.
Designed for operation with the varying voltages.
Depending on installation the SRL-3 can be used in CAT-4 / SIL 3 safety circuits.





| Technical Specifications | |
|---|---|
| Reset Options | Manual / Automatic |
| Construction | Red Polycarbonate housing and terminals |
| Indication | LED's for Power & Output K1 & K2 |
| IP Rating | Housing IP40, Terminals IP20 |
| Weight | NA |
| Mounting | 35mm DIN Rail |
| Supply Voltage Options | 8-36VDC (+/- 15%) |
| Power Consumption | 3VA |
| Safety Output | 3 x NO |
| Safety Output Rating | 4A/230Vac; 2A/24Vdc(Res.)@Cos=1 |
| Auxilliary Output | 1 x NC |
| Auxilliary Output Rating | 4A/230Vac; 2A/24Vdc(Res.)@Cos=1 |
| Input | UP TO 30 DEVICES |
| Dimensions of Control Unit (mm) | 22.5 x 90 x 118.5mm |
| Environmental Specifications | |
| Operating Temperature | -10°C to 55°C |
| Storage Temperature | -20°C to 60°C |
| Safety Related Data | |
| PL in accordance with EN ISO 13849-1 | PL-e, CAT 4 |
| SIL CL in accordance with EN IEC 62061 | SIL 3 |
| PFHd in accordance with EN IEC 62061 | 3.62 x 10 -9 |
| PFH | 4.43 x 10 -9 |
| B10d | 2 x 10 -6 |
| MTTFd | High > 100 Years ( Based on usage rate of 360 Days |
| TM | 20 years |
| DC | 96.50% |
| SFF | 98.20% |
| File Title | File Name | Download File |
|---|---|---|
| 307 401 Iss1 Mechan SRL3 installation guide | 307-401-Iss1-Mechan-SRL3-installation-guide.pdf | PDF (543 KB) |